SECTION 2 Control Systems


201. General


1. The following requirements are to apply systems.


to well control systems, drilling systems and control

(1) The control system (hydraulic, pneumatic, electric, electro-hydraulic, acoustic, etc.) is to be de- signed where no single control system component failure is to lead to a failure of the con- trolled system or loss of control.

(2) Transfer between control stations is to comply with the following requirements.

(A) Transfer between control stations only applies to drilling control systems and does not apply to BOP, EDS, choke and kill, and diverter control systems.

(B) Transfers between control stations are to comply with the following.

(a) When control of the system or equipment is possible from more than one control loca- tion, control is to be possible only from one control location at a time.

(b) Clear method to transfer control between stations is to be provided.

(c)

At each control location, there is to be an indicator showing which location is in

control.

(3) Maximum control system voltages: 250 VAC 50 Hz or 60 Hz or d.c. voltage is to be the highest voltage in any of the control system panels.

(4) All safety functions are to be provided with visual and audible indicators.

2. Logic circuit features

(1) Logic circuit is to comply with the following principles:

(A) When logic circuits are used

for sequential startup or for operating individual components,

indicators are to be provided at the control console to show the successful completion of

the sequence of operations by

the logic circuit and start-up and operation of the component.


Guidance Relating to the Rules for the Classification of Mobile Offshore Drilling Units 2015 69

image


If some particular step is not carried out during the sequence, the sequence is to stop at this point.

(B) Manual override is to be fitted in vital functions to permit control in the case of failure of

a logic circuit.


202. Control systems for well control equipment


1. Control systems for well control include the BOP, EDS, choke and kill and diverter control systems. These control systems are to comply with the following requirements:

(1) The control system (hydraulic, pneumatic, electric, electro-hydraulic, acoustic, etc.) is to be de- signed where no single control system component failure is to lead to a failure of the con- trolled system, loss of control or loss of well control.

(2) The control system and components are to be in compliance with API Spec 16C, API Spec 16D and with applicable recommended practices such as API RP 53, API RP 59, and API RP 64.

(3) Ch 4, 202. 3, 203. 9 and 204. 5 are to apply to control system requirements for individual well control systems and/or equipment.

(4) FMEA, FMECA or similar analysis is also to be conducted to determine compliance with (1)

to (3) and Ch 4, Sec 2.


203.

Electrical Control Systems and Computer-Based Systems


1. Electrical control systems

(1) Electrical control systems are to comply with Pt 6, Ch 2, 204. 4 of Rules for the Classification of Steel Ships.

(2) In addition, electrical control systems are to comply with 204.

2. Computer-based Systems

(1) Computer-based systems are to comply with Pt 6, Ch 2, 201. 7.

(2) In addition, computer-based systems are to comply with the following.

(A) Fail Safe Computer-based systems are to be designed such that any of the system's compo- nents will not cause unsafe operation of the system or equipment being controlled.

(B) Failure Modes and Effects Analysis (FMEA) An FMEA is to be used to determine that any component failure will not result in the complete loss of control, the shutdown of the system or equipment being controlled, or other unsafe situation.

(C) Failure Mode, Effects and Criticality Analysis (FMECA) An FMECA is an extension of the FMEA to include a criticality analysis that is used to identify the probability of fail- ure modes against the severity of their consequences.

(D) Safety Integrity

(a) When computer-based systems have safety-related control functions and the associated failure modes identified in the FMEA/FMECA result in an undesirable situation, special consideration may be given, provided the appropriate level of safety integrity has been provided.

(b)


(c)

The appropriate level is to be determined by the application of recognized industry standard, such as the IEC 61508 Series or the ANSI/ISA 84 Series.

Documentation in accordance with the relevant industry standard is to be submitted for

review to justify the appropriate safety integrity levels.


204.

Safety systems


1. Means are to be provided to indicate the cause of the safety action.


2. Alarms are to be given at each control location, including any local manual control positions, upon the activation of a safety system.


3. Drilling systems or equipment shutdown by a safety system is to be designed not to restart auto- matically, unless first actuated by a manual reset.


4. Systems are to have the following:

(1) Redundant processor, memory, and networks


70 Guidance Relating to the Rules for the Classification of Mobile Offshore Drilling Units 2015

image


(2) Local and remote I/O modules are to fail in a predetermined fashion when there is loss of communications with the CPU.

(3) Input and Output points are to be diagnostic type, where the program will read the diagnostic

status of the I/O and perform safe actions. The program is to notify the operator fails.

5. All shutdowns are to be executed in a predetermined logical manner, as specified in the Logic", and are to indicate or execute actions to:

(1) Limit the severity of the incident

(2) Protect personnel

(3) Limit environmental impact

(4) Escape, muster, and evacuation process

6. Shutdown is not to result in adverse cascade effects, which result from activation of tection devices to maintain the facility in a safe condition.


7. The shutdown systems are to be designed to provide that any ongoing operations can be safely when a shutdown is activated.

if a point


"Shutdown


other pro- terminated

8. Adequate measure is to be provided to prevent accidental unlatching of the wellhead connector,

emergency disconnect, and LMRP, such equivalent.


image

9. Control panels are to be clearly labeled.

as two-hand function, two-step action, protective cover or


Guidance Relating to the Rules for the Classification of Mobile Offshore Drilling Units 2015 71