4. Fire control plans are to be submitted for review on which the following, as a minimum, should be clearly shown:

(1) Locations of fire control stations;

(2) Various fire sections enclosed by various classes of fire divisions;

(3) Arrangement

of fire detectors and manual fire alarm stations;

(4) Arrangement of combustible gas detectors;

(5) Arrangement of hydrogen sulphide gas detectors;

(6) Locations of respiratory protection equipment for hydrogen sulphide;

(7) General alarm actuating positions;

(8) Arrangement of various fire-extinguishing appliances;

(9) Locations of Fighter’'s Outfits;

(10) Location of Helicopter Crash Kit;

(11) Arrangement of water spray nozzles and sprinklers (if fitted);

(12)

Locations of emergency shutdown (such as oil fuel source shutdown, engine shutdown, etc.)

stations;

(13) The Ventilating system including Fire dampers positions, Ventilating Fans control positions with indication of identification numbers of Ventilating Fans serving each section;

(14) Arrangement of fire/watertight doors and their remote control positions;

(15) Blowout preventer control positions;

(16) Escape route and means of access to different compartments, decks, etc.;

(17) Locations of Emergency Escape Breathing Devices (EEBD); and

(18) Arrangement of emergency muster stations and life-saving appliances.


102. Alternative design and arrangements

When fire safety design or arrangements deviate from the prescriptive provisions of the Code, en- gineering analysis, evaluation and approval of the alternative design and arrangements should be carried out in accordance with SOLAS regulation II-2/17.