3. The fire detection main indicator board is to be at a manned control station and is to be clearly to indicate where fire has been detected.
4. An automatic fire detection and alarm system is to be provided in all accommodation and service spaces. Accommodation spaces are to be fitted with smoke detectors. Thermal detectors are to be fitted in galleys.
5. A fixed fire detection and fire alarm system should be installed in:
(1) periodically unattended machinery spaces; and
(2) machinery spaces where:
(A) the installation of automatic and remote control system and equipments has been approved in lieu of continuous manning of the spaces, and
(B) the main propulsion and associated machinery, including the main sources of electrical pow- er, are provided with various degrees of automatic or remote control and are under con-
tinuous manned supervision from a control room.
(3) enclosed separate spaces containing incinerators
6. Smoke detectors are to be provided in all electrical rooms and control stations.