CHAPTER 9 FIRE PROTECTION, MEANS OF ESCAPE AND FIRE EXTINCTION
Section 1 General
Section 2 Fire Protection and Means of Escape
Section 3 Fire Detection and Extinction
1. Spaces having a fire risk, in principle, are to be provided with an automatic alarm system.
3. The fire detection main indicator board is to be at a manned control station and is to be clearly to indicate where fire has been detected.
7. Sufficient manual fire alarm stations are to be installed throughout the accommodation spaces, service spaces and control stations. One manually operated call point is to be located at each exit. Manually operated call points are to be readily accessible in the corridors of each deck such that no part of the corridor is more than 20 m from a manually operated call point. Measures are to be taken to prevent inadvertent operation of the manual call alarm system.
Section 4 Fire Extinguishing Systems for Helicopter Facilities
(5) the fire fighting systems equipment as given in 402. are to be provided and so arranged as to adequately protect both the helicopter deck and fuel storage areas.
Section 5 Gas cylinders
Section 6 Offshore Accommodation Unit